Buying a Small Ontario Plaza? The Fire Code Records the Seller Should Be Able to Hand You

During a conditional period you cannot test a sprinkler system yourself. What you can test is the paper trail, and the Ontario Fire Code tells you exactly which pieces of paper ought to exist.

Arthur Zhao · Broker · AZ Real Estate Partners · 2026-10-05
Quick Answer

Which fire-safety records should already exist for a small Ontario commercial building with extinguishers, a fire alarm and sprinklers?

Read it as a matrix: for each system, the Fire Code fixes who is responsible (the owner, defined by control), what is done, how often, and therefore what paper must be on file. Under Division B 1.1.2, every required test produces a record kept at the building for at least two years, with at least the latest and the previous record of each test retained.

System Who Does what, how often Paper that should exist
Portable extinguishers Owner (control) Inspect monthly; maintain to NFPA 10 Service tag on each unit, or approved records
Fire alarm Owner, using a technician who meets Division C Inspect and test to CAN/ULC-S536 (annual); check the control facility daily Device-by-device test record, current system description, technician certificate on request
Sprinklers Owner (control) Weekly gauge check; NFPA 25 or the Code’s own monthly/annual schedule Approved inspection record for each system
Emergency lights and exit signs Owner (control) Monthly and 12-month checks Test records

Source: Ontario Fire Code, O. Reg. 213/07, Division A 1.4.1.2; Division B 1.1.2, 6.2.7, 6.3.2, 6.5, 6.7.1; Division C 1.2.1.2 (e-Laws)

I’m Arthur Zhao, a real estate broker in Toronto. Picture the data room for a two-storey plaza with ten units: rent roll, leases, a tax bill, a roof report. Then a folder labelled “Fire”, holding a single invoice from a sprinkler contractor.

That one invoice tells you a contractor was paid. It does not tell you whether the alarm panel was tested last year, whether the person who tested it was qualified, or whether the emergency lights would stay on during a power cut. You cannot run those tests yourself before waiving conditions. What you can do is ask for the records the Fire Code already requires the current owner to keep, and notice which ones are missing. This article turns those record-keeping rules into a request list.

Ask: which systems does the building have?

→

Map each system to its Fire Code testing rule

→

Request the records that rule should have produced

→

Note the gaps and who controls each space after closing

Why the paper trail is the inspection you can actually do

The Ontario Fire Code is O. Reg. 213/07, made under the Fire Protection and Prevention Act, 1997. Its Part 6 (in Division B) covers the “installation, checking, inspection, testing, maintenance and operation” of fire protection equipment and life safety systems.

Two record-keeping rules make Part 6 useful to a buyer:

  • Making records (1.1.2.1): wherever the Code requires tests and corrective measures, a record must be made of what was done and the date and time. Records are kept at the building for the Chief Fire Official; electronic records that can be produced readily on request also comply.
  • Keeping records (1.1.2.2): each required record is kept for at least two years, and in any case the most recent and the immediately preceding record of each test must be on hand. For fire protection systems installed after November 21, 2007, the initial verification or test reports are kept for the life of the system.

So a building in compliance should be able to show you roughly two years of history for each system, plus, for newer systems, the original commissioning paperwork. That is the yardstick for everything below.

ℹ️Records may live in a portal. Division B 1.1.2.1(4) accepts electronic records if they can be made readily available to the Chief Fire Official on request. A seller who says “it’s all online with our service company” can satisfy the rule, provided the records can actually be pulled up when asked.

Fire alarm: the annual report and the person who signed it

According to O. Reg. 213/07, Division B 6.3.2.2, a fire alarm system is inspected and tested in conformance with CAN/ULC-S536, “Standard for Inspection and Testing of Fire Alarm Systems”. The Code then spells out what should come out of that process. Ask for:

  • The latest two annual inspection and test reports, with a record for each device, component and circuit stating whether it is in proper working order (6.3.2.2(4)).
  • The current system description, which must be kept up to date and stored in the building at an approved location (6.3.2.2(3)).
  • Monitoring receipts, if the system sends signals to the fire department through a monitoring station: the owner must record whether the test signals were received (6.3.2.2(5)).
  • The technician’s course certificate. Under 6.3.2.1 and Division C 1.2.1.2, the person doing the annual test must have completed a program or course acceptable to the Fire Marshal (or work under the on-site supervision of someone who has, with no more than two people supervised at once), and must produce the certificate at the request of the owner or the Chief Fire Official. Division C 1.2.1.3(2) puts it on the owner to ensure this is met.

The Code also requires the central alarm and control facility to be checked daily for trouble indications (6.3.2.3). It is worth asking who does that check and how it is logged.

Sprinklers: one inspection record per system, and which schedule it follows

Division B 6.5.1.8 requires an approved record of inspections for each sprinkler system, available to the Chief Fire Official. What that record covers depends on which route the building takes:

  • The NFPA 25 route. Under 6.5.1.1(2), inspecting, testing and maintaining to NFPA 25 is deemed to satisfy Subsections 6.5.4 to 6.5.6. A contractor working this way may organize its reports around NFPA 25 rather than Fire Code article numbers.
  • The Code’s own schedule in those subsections: alarm tested monthly by flowing water through the test connection (6.5.5.2); a water-flow alarm test from the most hydraulically remote connection annually on wet systems (6.5.5.3); a main drain test with the valve fully open annually (6.5.5.5); and, where the system is electrically supervised, transmitters and water-flow devices tested every two months and valve supervisory switches and similar devices at least every six months (6.5.5.7).

Two rules sit outside the 6.5.4 to 6.5.6 range, so they apply whichever route is chosen: the weekly gauge check of water supply pressure and system air or water pressure (6.5.3.2), and the rule that control valves or water supplies cannot be shut down or impaired for more than 24 hours without notifying the Chief Fire Official (6.5.2.2(1)). Ask whether there has been any such shutdown in the past two years and, if so, for evidence of the notice.

Extinguishers and emergency lighting: the records you can partly check on a walk-through

These are the two systems where your own eyes help, because some of the evidence hangs on the wall.

Portable extinguishers (Section 6.2). Maintenance and testing follow NFPA 10 (6.2.7.1), and extinguishers are inspected monthly (6.2.7.2). Each unit carries a tag showing the maintenance or recharge date, the servicing agency and the signature of the person who did the work, unless other approved records show the same things (6.2.7.4). On a tour, read the tags. Units near cooking operations should be rated for Class K fires (6.2.6.12), and units in or near electrical service rooms for Class C (6.2.6.13).

Emergency lighting and exit signs (Section 6.7). Self-contained emergency lighting units are inspected and tested at intervals of no more than one month, and tested at intervals of no more than 12 months to confirm they run for their design duration on simulated power failure (6.7.1.6). Other emergency lights are inspected at least every 12 months (6.7.1.7). Exit signs are inspected every 12 months; those with battery back-up are checked monthly and every 12 months (6.7.1.8). Ask for both the monthly log and the most recent 12-month duration test, because they answer different questions.

The fire safety plan: first check whether the building is on the list

A fire safety plan is not required in every commercial building. Division B 2.8.1.1 lists the buildings it applies to. For a typical plaza, the relevant lines are:

  • an assembly occupancy (no occupant-load threshold on the list);
  • a business and personal services occupancy, or a mercantile occupancy, where the occupant load exceeds 300;
  • a high-hazard industrial occupancy over 25, medium-hazard over 100, low-hazard over 300;
  • buildings with 4 storeys or more, counting storeys below grade, plus several other specific triggers in 2.8.1.1(2).

The trigger is occupancy type and occupant load or height. It is not whether the building has a fire alarm; the only alarm-linked item on the list is for agricultural buildings. If the building is on the list, ask for the plan itself, which must be prepared, approved by the Chief Fire Official and implemented (2.8.2.1(1)), kept in the building at an approved location (2.8.2.1(3)), and reviewed at least every 12 months (2.8.2.1(4)). Ask for evidence of the most recent review.

⚠️Do not assume a small plaza is off the list. An assembly occupancy appears in 2.8.1.1 with no occupant-load threshold, so how each unit is classified matters more than the total number of units or storeys.

💡 My own view: a missing record is a finding in its own right, not a gap to shrug at. First, it is a compliance problem by itself, because 1.1.2 requires the record to exist and stay at the building. Second, from where a buyer sits, “the equipment is fine” and “nobody checked” look exactly the same when the paper is missing. You cannot tell them apart, so it is reasonable to price or condition the deal as if you cannot. And third, the gap does not stay with the seller. Once you close and take control of the base building, the next inspection, and the next record, are yours to produce.

After closing: who the Fire Code treats as the owner

Division A 1.2.1.1 says that unless otherwise specified, the owner carries out the Code. Division A 1.4.1.2 defines owner as any person, firm or corporation having control over any portion of the building or property, including the persons in it. Ownership on title is not the test; control is.

Reading that definition directly, a plaza can have more than one Fire Code owner at the same time: whoever controls the common corridor and the sprinkler riser, and a tenant who controls its own unit. This is an inference from the wording, not a ruling on any specific building. A lease can allocate testing work and cost between landlord and tenant, so read the repair and compliance-with-laws clauses. But that is a contract between the two of them; it does not narrow who the Code reaches, which still turns on control.

Compare the residential rule in Division B 2.13.1.2: for smoke alarms in a rental suite, the Code says that only the landlord is considered the owner, despite the general definition. There is no equivalent carve-out for commercial premises. When you build your closing checklist, write down, system by system, who will control it on the day after closing.

What non-compliance can cost: the statutory maximums

According to the Fire Protection and Prevention Act, 1997 (s.28, as amended in 2019), contravening the Fire Code is an offence. The current penalty levels came from 2019, c. 7, Schedule 29, which came into force on June 28, 2019 (30 days after Royal Assent on May 29, 2019). The maximums are:

  • Individual: up to $50,000 for a first offence and $100,000 for a subsequent offence, or up to one year in prison, or both (s.28(3)).
  • Corporation: up to $500,000 for a first offence and $1,500,000 for a subsequent offence (s.28(4)).
  • Director or officer who knows the corporation is violating the Fire Code: up to $50,000 / $100,000, or up to one year, or both (s.28(5)).

These are ceilings set by the statute, not typical amounts.

Frequently Asked Questions

Q

The seller says all the fire records are with the property management company. Is that a problem?

A

Not by itself. The Fire Code (Division B 1.1.2.1) requires records to be retained at the building for the Chief Fire Official, and electronic records that can be produced readily on request are deemed to comply. What matters for a buyer is that copies can actually be produced during the conditional period, covering at least two years and the last two records of each test.

Q

Does a vacant commercial unit still need fire extinguishers?

A

The only exception stated for the extinguisher section is in Division B 6.1.1.2: Section 6.2 does not apply to dwelling units. A vacant shop is not on that exception. Any extinguishers that are in place remain subject to the monthly inspection rule in 6.2.7.2 and the tagging rule in 6.2.7.4.

Q

In a multi-tenant plaza, who counts as the owner for the common hallway versus each unit?

A

The Fire Code defines owner by control: anyone having control over any portion of the building (Division A 1.4.1.2). Read directly, the party controlling the common areas and shared systems and a tenant controlling its own unit can each be an owner for their portion. The lease decides who pays and does the work between them; it does not change who the Code applies to.

Q

The building has 2 storeys and 10 shops. Does it need a fire safety plan?

A

Check the list in Division B 2.8.1.1. Two storeys is under the 4-storey trigger, and business or mercantile occupancies only appear once occupant load exceeds 300. But any assembly occupancy is on the list with no threshold, and 2.8.1.1(2) has other triggers, so the answer depends on how each unit is classified.

Q

What is the maximum fine for breaking the Ontario Fire Code?

A

Under s.28 of the Fire Protection and Prevention Act, 1997, an individual faces up to $50,000 for a first offence and $100,000 for a subsequent one, or up to a year in prison, or both. A corporation faces up to $500,000 and $1,500,000. Those levels have applied since June 28, 2019.